Schneider 65ka 2P AC Surge Protective Devices

In Stock

The Schneider Electric 65KA 2P AC Surge Protective Devices are designed to provide protection for electrical and electronic equipment from transient overvoltage events caused by lightning strikes, power utility switching, or other sources of voltage surges. These surge protective devices (SPDs) are specifically tailored for use in alternating current (AC) applications, offering robust protection for sensitive equipment such as HVAC systems, industrial machinery, and other AC power sources.

  • Delivered today (order Mon-Fri before 12:00, delivery between 17:00 and 22:00)
  • Including shipping costs, sent by klbtheme.com
  • Pick up at a klbtheme.com collection point is possible
  • 30 days to change your mind and free returns
  • Day and night customer service
SKU: I5U2E1W3C7

Description

Schneider 65ka 2P AC Surge Protective Devices

The Schneider Electric 65KA 2P AC Surge Protective Devices are designed to provide protection for electrical and electronic equipment from transient overvoltage events caused by lightning strikes, power utility switching, or other sources of voltage surges. These surge protective devices (SPDs) are specifically tailored for use in alternating current (AC) applications, offering robust protection for sensitive equipment such as HVAC systems, industrial machinery, and other AC power sources.

With a high surge capacity of 65KA (kiloamperes), these SPDs offer reliable protection against large voltage surges that can potentially damage connected equipment. The 2P designation indicates that the devices have two poles, which allows them to protect both the live and neutral lines in an AC circuit.

Schneider Electric’s SPDs are built with advanced technology to ensure rapid response times to overvoltage events. This enables them to divert excess energy safely away from protected devices, helping to safeguard valuable equipment and minimize downtime due to electrical damage.

It’s important to remember that proper installation and regular maintenance of surge protective devices are essential for effective protection. Additionally, adherence to local electrical codes and standards is crucial when integrating SPDs into an AC power system.

In summary, the Schneider Electric 65KA 2P AC Surge Protective Devices offer dependable surge protection for AC applications while contributing significantly towards ensuring the reliability and longevity of connected electrical and electronic components.

This Acti9 iPRD8 surge arrester protects 2P installations. It allows quick replacement of damaged cartridges. The Imax maximum discharge current is 8kA .The In nominal discharge current is 2.5kA. The iPRD8r ensures secondary protection of loads to be protected and is placed in cascade with the incoming surge arresters. This surge arrester is required when the loads to be protected are at a distance of more than 10 m from the incoming surge arrester. The Uc maximum continuous operating voltage in common mode (between phase and earth) is 350VAC. The Up Voltage protection level in common mode (between phase and earth) is 1kV. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 36mm x (H) 85mm x (D) 69mm. The weight is 216g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.

Specifications

Main
range of product Acti9
Product name Acti9 iPRD
Product or component type Surge arrester with pluggable cartridge
Device short name iPRD8
Device application Distribution
Standards EN 61643-11:2012
IEC 61643-11:2011
Product certifications CE
Quality labels KEMA-KEUR
NF
poles description 2P
Remote signalling Without
Surge arrester type Electrical distribution network
Earthing system TN-C-S
Complementary
Surge arrester class type Type 2 + 3
Surge arrester technology MOV
[Ue] rated operational voltage 230 V AC (+/- 10 %) at 50/60 Hz
[In] nominal discharge current Common mode: 2.5 kA (L/PE)
Common mode: 2.5 kA (N/PE)
[Imax] maximum discharge current Common mode: 8 kA L/PE
Common mode: 8 kA N/PE
[Uoc] open circuit voltage 10 kV type 3 common mode L/PE
10 kV type 3 common mode N/PE
[Uc] maximum continuous operating voltage Common mode: 350 V L/PE
Common mode: 350 V N/PE
Maximum [Up] voltage protection level Common mode <1 kV type 2 L/PE
Common mode <1 kV type 2 N/PE
Common mode <1 kV type 3 L/PE
Common mode <1 kV type 3 N/PE
[Ut] temporary overvoltage 337 V L/N 5 s withstand
1200 V N/PE 200 ms safe failure mode
Disconnector device type Associated circuit breaker iC60L 10 A curve C – Icu 25 kA
Associated circuit breaker IC60N 10 A curve C – Icu 10 kA
Associated circuit breaker iC60H 10 A curve C – Icu 15 kA
Associated fuse gG 25 A – Icu 15 kA
Associated fuse gG 80 A – Icu 50 kA
Mounting mode Clip-on (DIN rail)
9 mm pitches 4
Height 85 mm
Width 36 mm
Depth 69 mm
Net weight 0.216 kg
Colour White (RAL 9003)
[Ipe] Ground residual current 0.6 mA
0.003 mA
Connections – terminals Tunnel type terminal (downside) 2.5…35 mm²
Tunnel type terminal (upside) 2.5…35 mm²
Tightening torque 2.5 N.m
Environment
IK degree of protection IK03 conforming to IEC 62262
Relative humidity 5…95 %
Operating altitude 2000 m
Ambient air temperature for operation -25…60 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 4.2 cm
Package 1 Width 7.2 cm
Package 1 Length 9 cm
Package 1 Weight 246 g
Unit Type of Package 2 BB1
Number of Units in Package 2 6
Package 2 Height 9.8 cm
Package 2 Width 8.5 cm
Package 2 Length 28 cm
Package 2 Weight 1.56 kg
Unit Type of Package 3 S03
Number of Units in Package 3 54
Package 3 Height 30 cm
Package 3 Width 30 cm
Package 3 Length 40 cm
Package 3 Weight 14.553 kg
Contractual warranty
Warranty 18 months

Reviews

There are no reviews yet.

Be the first to review “Schneider 65ka 2P AC Surge Protective Devices”

Your email address will not be published. Required fields are marked *